Single Phase PDU Specifications
| Single
Phase Filter Insertion Loss [dB into 50 ohms] |
| Frequency |
100
KHz |
500
KHz |
1
MHz |
5
MHz |
10
MHz |
20
MHz |
| Line-to-Ground
(Common Mode) |
15 |
40 |
45 |
64 |
80 |
70 |
| Line-to-Neutral
(Differential Mode) |
22 |
35 |
42 |
50 |
50 |
50 |
Operating
Frequency: 50-60Hz
Filtering: Primary phase, neutral, and Ground |
Leakage
Current: 1.5 mA @ 250VRMS
Discharge Voltage: 30 V max after 1 sec |
|
Circuit Breaker
Two pole magnetic-hydraulic breaker, medium trip delay
Surge Protection
Each PDU equipped with 70 Joule surge suppressor
Power Entry Connector
Two pole/three wire (2P/3W) "locking" flanged inlet
Line cord length: 6 Ft
See Model
Selection Table for NEMA Mating Connector
Output Receptacles
Four (4) duplex NEMA 5-20R
30 Amp Models: each output receptacle wired with supplementary 20 Amp
push-to-reset breaker
220 VAC Model: four (4) duplex NEMA 6-20R
Utility Receptacle
Each PDU provided with one additional duplex receptacle activated by main
circuit breaker
Dimensions
3.5" [H] x 19.0" [W] x 7.1" [D]
Operating Frequency
All single PDUs may be operated at 50 or 60 Hz
AC Power Input Configuration